[Bldg-sim] VAV with FP Boxes

James Hansen JHANSEN at ghtltd.com
Wed Oct 1 05:15:03 PDT 2008


At first glance, I would double check your insulation and window
values....you've got glass with a U-value of 1.2, exterior wall
insulation of R-3, and roof insulation of LESS than R-1.  This is partly
why your heating energy consumption is so large.

In addition, values like this will mean that your max zone supply
temperature of 95, and max reheat of 42 degrees, are probably not going
to be sufficient to heat the space to 70 degrees at all times.

GHT Limited
James Hansen, PE, LEED AP
Senior Associate
1010 N. Glebe Rd, Suite 200
Arlington, VA  22201-4749
703-338-5754 (Cell)
703-243-1200 (Office)
703-276-1376 (Fax)
www.ghtltd.com


-----Original Message-----
From: bldg-sim-bounces at lists.onebuilding.org
[mailto:bldg-sim-bounces at lists.onebuilding.org] On Behalf Of Dug Gwalt
Sent: Tuesday, September 30, 2008 6:53 PM
To: bldg-sim at lists.onebuilding.org
Subject: [Bldg-sim] VAV with FP Boxes

I've been beating my head against the wall trying to figure this out.
The attached inp and pd2 file are the 90.1 baseline for a model which
works.  I have many many unmet heating hours.  The ctrls options were
not changed between my design and the baseline, only the system type.
Can someone with more equest experience help me?



      

The information contained in this communication is confidential, may be privileged, and is intended only for the use of the addressee.  It is the property of GHT Limited.  Unauthorized use, disclosure or copying of this communication or any part thereof is strictly prohibited and may be unlawful.  If you have received this communication in error, please notify me immediately by return e-mail or by e-mail to ght at ghtltd.com, and destroy this communication and all copies thereof, including all attachments.  Thank you.