I get that error when I do novel things, too, and it goes away when I change
the loop sizing type from secondary (the default) to primary.  You may get a
warning afterwards that says that the loop is undersized for the connected
load.  I ignore these warnings since the loop is sized based on the primary
equipment capacity (which should be sufficient).

 

I hope this is helpful!

 

Eric

 

Ph:   (781) 431-1100 ext 12
Fax:  (781) 431-1109

 

  _____  

From: bldg-sim-bounces at lists.onebuilding.org
[mailto:bldg-sim-bounces at lists.onebuilding.org] On Behalf Of Alan Jackson
Sent: Monday, August 10, 2009 4:53 PM
To: bldg-sim at lists.onebuilding.org
Subject: [Bldg-sim] Thermal Storage Controls

 

I am modelling the cost benefits of creating chilled water/ice at night so I
have added a thermal storage tank and set up a secondary chiller and loop to
serve the storage tank. I have assigned an on/off schedule to the TES
chiller so that it operates only at night, but I have also added equipment
controls so that it has first priority for cooling. This was my initial
thought on getting it to operate at night but not during the day. I am
getting an error "Ice Water Loop has zero design flow". At first I figured
this was because I had no size for the storage tank selected so I started
off small and through a 50 ton tank in the capacity field. Still receiving
the same error. Does this have to be sized manually?

 

Here are the controls:

 

"Chiller Controls" = EQUIP-CTRL      

   TYPE             = COOLING

   CIRCULATION-LOOP = "Chilled Water Loop"

   CHILLERS-1       = ( "Ice Chiller" )

   CHILLERS-2       = ( "Air Cooled Chiller 1" )

   ..

 

and the tank

 

"Ice Storage" = THERMAL-STORAGE 

   TYPE             = COLD-WATER-TANK

   CAPACITY         = 600

   CHRG-LOOP        = "Ice Water Loop"

   CHRG-SCH         = "Ice Making Schedule Annual"

   DCHRG-LOOP       = "Chilled Water Loop"

   ..

 

 

 

Thanks in advance

 

 

 

Alan Jackson, LEEDR A.P. 

Senior Mechanical Engineer

Buro Happold Consulting Engineers, PC

100 Broadway 

New York, NY 10005

USA

 

Tel: (+1) 212 334 2025

Direct: (+1) 212 616 0267

Fax: (+1) 212 334 5528

Email: alan.jackson at burohappold.com
www.burohappold.com <http://www.burohappold.com/> 

 

This transmission is confidential and intended solely for the person or
organization to whom it is correctly addressed. If you are not the intended
recipient of this transmission, you should not take any action in reliance
on it. Further, this transmission may contain confidential design and other
information owned by Buro Happold Consulting Engineers PC. You should not
copy, distribute, use, offer for sale or hire such information or in any way
infringe the design and intellectual property rights of Buro Happold
Consulting Engineers PC. It is intended that communication by email from
Buro Happold Consulting Engineers PC or its employees is limited to
communications connected to the services provided by Buro Happold Consulting
Engineers PC. Buro Happold Consulting Engineers PC accepts no liability for
any communications not connected to the services it provides. Computer
viruses may be transmitted or downloaded onto your computer system via email
communication. It is the recipient's responsibility to take any action
necessary to prevent computer viruses being transmitted in this way.
Accordingly, Buro Happold Consulting Engineers PC disclaims all
responsibility which arises directly or indirectly from such transmission of
computer viruses.

 

 

This message has been scanned by MailController
<http://www.mailcontroller.altohiway.com/> .

-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/bldg-sim-onebuilding.org/attachments/20090811/a3939ed4/attachment-0001.htm>


More information about the Bldg-sim mailing list