The project has 4 rooftop units, and one ERV that provides OA to the 
four roof top units.  Except the ERV only provides 50% of the minimum 
OA for each of the four rooftop systems.  DOE2.2 and DOE2.1e do not 
seem to handle heat recovery in a make-up air system using the 
OA-FROM-SYSTEM command.  The way I typically handle this arrangement 
is to prorate the heat recovery effectiveness and the ERV fan power 
to each of the 4 roof top systems.  The 4 rooftop systems have 
typical OA % for an office building - less than 50%.  My 
interpretation of 90.1-1999 Section 6.3.6.1 is that the ERV has more 
than 5000 cfm and more than 70% OA (the ERV is 100% OA), therefore 
the Budget building ERV requires heat recovery at 50%.  To model 
this, the Budget building will have prorated heat recovery at the 4 
roof top units - again because one can't properly model a make-up air 
system with heat recovery using equest (DOE2.2) or DOE2.1e.

Does this make sense?