Hi Brian,

 

The 90.1 User's manual Table G-B, which I've come to regularly reference
for LEED projects instead of trying to force 25% process loads into my
models, lists parking garages as having a receptacle power density of
"NA" (distinct from the other entries).  If you are unaware of any
specific receptacle loads to include, I'd infer from this and the
accompanying text that you're not expected to model any.*  

 

Your process loads overall would still include any garage ventilation
fans, elevators, mechanical bollards, moving walkways, escalators, car
washes, mechanized street sweeping monkeys and so on.  

 

~Nick

 

* Small disclaimer:  The review process being what it is, nobody can
guarantee a reviewer that will force their personal interpretations down
your throat won't be assigned to your project.  The best you can do is
to document plainly any interpretations you have to make, and
cite/reference as you must to make your case clearly rational.  

 

 

 

NICK CATON, E.I.T.

PROJECT ENGINEER

25501 west valley parkway

olathe ks 66061

direct 913 344.0036

fax 913 345.0617

Check out our new web-site @ www.smithboucher.com 

 

From: bldg-sim-bounces at lists.onebuilding.org
[mailto:bldg-sim-bounces at lists.onebuilding.org] On Behalf Of Brian Tysoe
Sent: Wednesday, September 08, 2010 3:57 PM
To: 'bldg-sim at lists.onebuilding.org'
Subject: [Bldg-sim] Parking Structure LEED Energy Model

 

Hi,

 

I am working on a preliminary LEED energy model for a six-story 500,000
square foot parking structure. The parking area is unheated. The major
energy usage is lighting; followed by heating of stairs, elevator
lobbies, storage, etc.

 

Do I have to consider a 25% process load? What would that be?

 

Thanks,

 

 

Brian Tysoe M.A.Sc., P.Eng., LEED AP 

Mechanical Engineer 

 

MCW Consultants Ltd. <http://www.mcw.com> 

600-156 Front Street West 
Toronto, ON M5J 2L6 
Phone 416-598-2920 
Fax 416-598-5394 

 

This e-mail may be privileged and confidential. Any unauthorized use is
strictly prohibited. If you received this e-mail in error, please
contact the sender directly. 

 

-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/bldg-sim-onebuilding.org/attachments/20100908/a96134b1/attachment-0002.htm>
-------------- next part --------------
A non-text attachment was scrubbed...
Name: not available
Type: image/jpeg
Size: 1459 bytes
Desc: image001.jpg
URL: <http://lists.onebuilding.org/pipermail/bldg-sim-onebuilding.org/attachments/20100908/a96134b1/attachment-0002.jpeg>


More information about the Bldg-sim mailing list