[Equest-users] Fw: ERV on OA-From-System Comments from Jeff Hirsch

Paul Diglio paul.diglio at sbcglobal.net
Tue Jun 4 13:00:46 PDT 2013


Rick:

Thanks for the response.  I have tried what you are suggesting and have not been 
successful in modeling the same energy recovery results that manual calculations 
indicate should be achieved.  It seems to me that the return airflow is from the 
zone that the DOAS is attached to and not the other zones, as indicated by the 
return air temperature.  In other words, it lloks like the only heat availabe 
for recovery is from the zone or dummy zone served by the DOAS.

I would be interested in looking at one of your projects if you care to share 
one.

If the eQuest developer, Jeff Hirsh tells me that an OA-From with an ERV is not 
supported, I will have to take him at his word.  He did not say what aspect is 
not supported.  Like I said, in the past I have chopped up the ERV and attached 
a smaller one to each system served and achieved the results that my manual 
calculations indicated would be achieved.   I am just at a loss with a DOAS that 
has chilled and hot water coils as well as an ERV, since the coils have been 
sized assuming that the ERV conditions the air previous to it entering the 
coils.

Without the ERV on the DOAS my discharge air temperature in the winter 
(Westfield, MA) is as low as 30 degrees and the chilled beams, modeled as IU, 
cannot supply the required discharge air temperature.  If I try to remove the 
coils from the DOAS and chop them up and increase the heating/cooling capacity 
of each chilled beam system, my discharge air off the DOAS drops as low as -5 in 
the winter and again the chilled beams with their mini ERV's cannot condition 
this air.

Any ideas?

Thank you,

Paul Diglio, CEM, CBCP


87 Fairmont Avenue
New Haven, CT  06513
203-415-0082


www.pdigliollc.com




________________________________
From: Rick Goeres <RickG at musgrovepa.com>
To: Paul Diglio <paul.diglio at sbcglobal.net>; equest-users at lists.onebuilding.org
Sent: Tue, June 4, 2013 11:06:19 AM
Subject: RE: [Equest-users] Fw: ERV on OA-From-System Comments from Jeff Hirsch


I have specified a DOAS as a single zone unit before and then designated it as 
the OSA From System in all of the other HVAC systems.  If I leave the Design 
Outdoor Air and Exhaust flow inputs empty under the heat recovery tab, the 
outside air from the other HVAC systems does not show up in the ERV.  But if I 
total the design outside air values and then input these into the Design Outdoor 
Air and Exhaust flows, the ERV works and seems to be representative.  
 
  Rick Goeres, PE, LEED AP  
 MUSGROVE ENGINEERING, P.A.
Web: www.musgrovepa.com
234 S. Whisperwood Way, Boise, ID 83709            
Ph: 208.384.0585 x324     Fx:208.384.0765
Over 35 Years of Engineering Excellence  
 
 
 
 
 
 
From:equest-users-bounces at lists.onebuilding.org 
[mailto:equest-users-bounces at lists.onebuilding.org] On Behalf Of Paul Diglio
Sent: Monday, June 03, 2013 5:54 PM
To: equest-users at lists.onebuilding.org
Subject: [Equest-users] Fw: ERV on OA-From-System Comments from Jeff Hirsch
 
 
 
 
Stormy:

In the past when I have modeled just an DOAS that did not have any heating or 
cooling capacity with and ERV was to add an ERV to each zone system that the 
DOAS fed.  I used the same kw/cfm that the DOAS system had.  So I chopped up the 
DOAS with it's ERV into smaller ERV's on each system.  This seemed to work good.

The problem with the project that I am working on now, is that the DOAS feeds 
chilled beams.  The DOAS chilled water coil and heating coil is sized in the 
design with the assumption that and ERV is conditioning the outside air.  The 
DOAS has to dehumidify the air because the chilled beams cannot remove moisture 
as there is no provision for condensate removal.  If I remove the ERV from the 
DOAS, the chilled and hot water coils are not large enough to condition the OA 
before it reaches the ERV on the chilled beams and I can't add a chilled or hot 
water coil to the ERV's on the chilled beams.  So I loose the additional 
heat/cool capacity designed into the DOAS.

Confusing.

Regards,
 
Paul Diglio, CEM, CBCP
87 Fairmont Avenue
New Haven, CT 06513
203-415-0082
 
www.pdigliollc.com
 
 

________________________________

From:Stormy L. Shanks <shankssl at kjww.com>
To: Paul Diglio <paul.diglio at sbcglobal.net>
Sent: Mon, June 3, 2013 7:15:24 PM
Subject: RE: [Equest-users] ERV on OA-From-System Comments from Jeff Hirsch
Wow, thank you for sharing that. That’s definitely a bummer. I just did a test 
on a model that I did with DOAS where I had defined an ERV in the DOAS system. I 
deleted the ERV from the system, and my energy was lower than when the ERV was 
included. Not good. I should have known better. I suppose I will start modeling 
ERV/DOAS settings in spreadsheets outside of eQUEST. Or in other software.
 
 Stormy L. Shanks, PE
Mechanical Engineer 
2882 106th St, Des Moines, IA 50322
D 515.334.4315 
web | Facebook | Twitter | LinkedIn  
 
 
From:equest-users-bounces at lists.onebuilding.org 
[mailto:equest-users-bounces at lists.onebuilding.org] On Behalf Of Paul Diglio
Sent: Monday, June 03, 2013 5:17 PM
To: equest-users at lists.onebuilding.org
Subject: [Equest-users] ERV on OA-From-System Comments from Jeff Hirsch
 
Just wanted to share an e-mail from Jeff.  I did not know that an ERV on a 
OA-From system was not supported by eQuest.  That explains why I could never get 
the correct airflows on this type of design.

Unfortunately almost every project I work on does specify a VAV DOAS with an ERV 
to supply ventilation air to some type of HVAC system, such as VRF indoor coils, 
chilled beams or PTHP units.  I will have to try the work around Jeff suggested.
 
Paul Diglio, CEM, CBCP
87 Fairmont Avenue
New Haven, CT 06513
203-415-0082
 
www.pdigliollc.com
 
 
----- Forwarded Message ----
From: Jeff Hirsch <James.J.Hirsch at gmail.com>
To: Paul Diglio <paul.diglio at sbcglobal.net>
Sent: Mon, June 3, 2013 12:17:58 PM
Subject: Re: [Equest-users] OA From System Question
Setting your OA system (ERU1) to be vav and having the ERV on it will not work 
correctly.  If you need ERV you must place your ERV in the IU system and use 
that system to supply the conditioned OA.  ERV on a OA-FROM system is not 
supported.  VAV on an OA-FROM system is possibly not what you want but I cannot 
tell what you are trying to do.  An IU system has a central constant volume air 
supply with each zone then having zone coil to do the zone thermostat controlled 
conditioning via room air flow induced as a constant ratio supply air fro the IU 
(the induction-ratio). So it seems you can use the IU system as your ERU system 
supplying the zones. If there is some other reason you used an OA-FROM system, 
then perhaps my suggestions don’t apply, but the ERV and VAV comments always 
apply.
 

________________________________

Jeff Hirsch
James J. Hirsch & Associates
12185 Presilla Road -  Camarillo, CA 93012-9243 USA
phone: (805) 553-9000 mobile: (805) 532-1045 fax: (805) 532-2401
email: James.J.Hirsch at gmail.com
 
From:Paul Diglio 
Sent:Monday, June 03, 2013 6:11 AM
To:equest-users at lists.onebuilding.org 
Subject:[Equest-users] OA From System Question
 
Morning:

I am trying to model a chilled beam system as induction units.  The primary air 
is supplied by an ERU.  I set the outside air to 0 on the chilled beams HVAC 
systems tab.

In the chilled beam zone tab I set the outside air to the primary CFM and the 
overall CFM to the induced air flow.

Per the eQuest help menu, "The sum of the OA requirements for all SYSTEMs that 
reference an OA-FROM-SYSTEM is used to set the referenced OA-FROM-SYSTEM value 
for MIN-OUTSIDE-AIR, SUPPLY-FLOW as well as adjust the referenced OA-FROM-SYSTEM 
directly served ZONE maximum and minimum flows for both heating and cooling." 


But per my hourly reports, the ERU is not supplying the necessary amount of 
primary air and in the summer the ERU flow drops to .01 CFM.

Attached are the project files.  Any ideas?

Thank you,
 
Paul Diglio, CEM, CBCP
87 Fairmont Avenue
New Haven, CT 06513
203-415-0082
 
www.pdigliollc.com 
 

________________________________

_______________________________________________
Equest-users mailing list
http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org
To unsubscribe from this mailing list send  a blank message to 
EQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG
 

________________________________

This message and any attachments contain information intended for a specific 
party and may include sensitive or confidential material. If you are not the 
intended recipient, please do not read, copy, use, or disclose to others. Please 
notify the sender of the delivery error by reply and then permanently delete 
this message and all attachments. 

  ­­   
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20130604/5503c1e6/attachment-0002.htm>
-------------- next part --------------
A non-text attachment was scrubbed...
Name: not available
Type: image/jpeg
Size: 1803 bytes
Desc: image001.jpg
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20130604/5503c1e6/attachment-0002.jpeg>
-------------- next part --------------
A non-text attachment was scrubbed...
Name: not available
Type: image/gif
Size: 346 bytes
Desc: image002.gif
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20130604/5503c1e6/attachment-0002.gif>
-------------- next part --------------
A non-text attachment was scrubbed...
Name: not available
Type: image/png
Size: 9229 bytes
Desc: image003.png
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20130604/5503c1e6/attachment-0002.png>


More information about the Equest-users mailing list