Hi Milan,
Yes, if you have it included in the Proposed building you should have it included in the Baseline as well. See Table G3.1, 1b. which requires the humidity control setpoints to be the same for proposed and baseline design. However, you can alter the humidification system to demonstrate energy savings (e.g., atomizing humidifiers, etc.).
S pozdravom,
Norbert Repka
Norbert Repka PhD.,
CGD, LEED(r) BD+C
Sustainable
AEI | AFFILIATED ENGINEERS, INC.
5802 Research Park Boulevard | Madison, WI 53719
P: 608.441.6644 | F: 608.238.2614
nrepka at aeieng.com<mailto:nrepka at aeieng.com> | www.aeieng.com<http://www.aeieng.com/>
From: Bldg-sim [mailto:bldg-sim-bounces at lists.onebuilding.org] On Behalf Of Milan Janak
Sent: Monday, October 27, 2014 8:04 AM
To: bldg-sim at lists.onebuilding.org
Subject: [Bldg-sim] Humidification in Baseline building
Importance: High
Dear All,
Should the humidification system be included in the Baseline building if it is present in the Propose building?
It is common practice to include humidification system in the 5A Climate zone here in Europe to keep relative
humidity above at least 35% in winter.
Regards,
Ing. Milan Janák, PhD. Simulácie Budov, s.r.o.
BREEAM Accredited Professional Čajakova 13
BREEAM Licensed Assessor 811 05 Bratislava
Member ASHRAE, CIBSE, SKGBC Slovakia
www.simulaciebudov.sk GSM: +421 (0)903 776 61
[logo_sim_breeam]
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/bldg-sim-onebuilding.org/attachments/20141027/d44267ac/attachment.htm>
-------------- next part --------------
A non-text attachment was scrubbed...
Name: image001.png
Type: image/png
Size: 60462 bytes
Desc: image001.png
URL: <http://lists.onebuilding.org/pipermail/bldg-sim-onebuilding.org/attachments/20141027/d44267ac/attachment.png>
More information about the Bldg-sim
mailing list