RE: [EnergyPlus_Support] ZoneHVAC:LowTemperatureRadiant:Electric





That surface’s construction has to be defined using Construction:InternalSource. 

 

From: EnergyPlus_Support@xxxxxxxxxxxxxxx [mailto:EnergyPlus_Support@xxxxxxxxxxxxxxx] On Behalf Of alterea_nrjplus
Sent: Tuesday, August 31, 2010 5:19 AM
To: EnergyPlus_Support@xxxxxxxxxxxxxxx
Subject: [EnergyPlus_Support] ZoneHVAC:LowTemperatureRadiant:Electric

 

 

Hey Users E+,

I'd like to use "ZoneHVAC:LowTemperatureRadiant:Electric".
I have a Severe error about the surface surface that I use in "LowTemperatureRadiant".
This surface is a valid "BuildingSurface:Detailed". It's the floor of my zone.

I don't understand this error message :

** Severe ** Construction referenced in Electric Radiant System surface does not have a source/sink present Surface name= S_1734_4_0_0 Construction name = 3

Can you help me please ? Thanks a lot



__._,_.___


Primary EnergyPlus support is found at:
http://energyplus.helpserve.com or send a message to energyplus-support@xxxxxxxx

The primary EnergyPlus web site is found at:
http://www.energyplus.gov

The group web site is:
http://groups.yahoo.com/group/EnergyPlus_Support/

Attachments are currently allowed but be mindful that not everyone has a high speed connection.  Limit attachments to small files.

EnergyPlus Documentation is searchable.  Open EPlusMainMenu.pdf under the Documentation link and press the "search" button.




Your email settings: Individual Email|Traditional
Change settings via the Web (Yahoo! ID required)
Change settings via email: Switch delivery to Daily Digest | Switch to Fully Featured
Visit Your Group | Yahoo! Groups Terms of Use | Unsubscribe

__,_._,___