[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [EnergyPlus_Support] Post processing on number of hours when room air temperature was more than 25[C]





Yes, just use time bins-- see example below. 

Name Comfort Report Energy Report Loads Report 
Digits After Decimal 1 1 1
Variable or Meter 1 Name Zone Thermal Comfort ASHRAE 55 Adaptive Model 80% Acceptability Status DistrictCooling:HVAC Zone Ideal Loads Supply Air Total Cooling Rate
Aggregation Type for Variable or Meter 1 HoursNonZero SumOrAverage SumOrAverage
Variable or Meter 2 Name Zone Thermal Comfort ASHRAE 55 Adaptive Model 90% Acceptability Status DistrictHeating:HVAC Zone Ideal Loads Supply Air Total Cooling Rate
Aggregation Type for Variable or Meter 2 HoursNonZero SumOrAverage Maximum
Variable or Meter 3 Name Zone Thermal Comfort CEN 15251 Adaptive Model Category I Status Ventilation (simple):Fans:Electricity Zone Ideal Loads Supply Air Total Heating Rate
Aggregation Type for Variable or Meter 3 HoursNonZero SumOrAverage SumOrAverage
Variable or Meter 4 Name Zone Thermal Comfort CEN 15251 Adaptive Model Category II Status InteriorLights:Electricity Zone Ideal Loads Supply Air Total Heating Rate
Aggregation Type for Variable or Meter 4 HoursNonZero SumOrAverage Maximum
Variable or Meter 5 Name Zone Thermal Comfort CEN 15251 Adaptive Model Category III Status Carbon Equivalent:Facility
Aggregation Type for Variable or Meter 5 HoursNonZero SumOrAverage
Variable or Meter 6 Name Zone Thermal Comfort Fanger Model PPD
Aggregation Type for Variable or Meter 6 SumOrAverageDuringHoursShown
Variable or Meter 7 Name Zone Thermal Comfort Fanger Model PMV
Aggregation Type for Variable or Meter 7 HoursPositive
Variable or Meter 8 Name Zone Thermal Comfort Fanger Model PMV
Aggregation Type for Variable or Meter 8 HoursNegative
Variable or Meter 9 Name Zone Thermal Comfort Fanger Model PMV
Aggregation Type for Variable or Meter 9 HoursZero
Variable or Meter 10 Name
Aggregation Type for Variable or Meter 10
Variable or Meter 11 Name
Aggregation Type for Variable or Meter 11
Variable or Meter 12 Name
Aggregation Type for Variable or Meter 12
Variable or Meter 13 Name
Aggregation Type for Variable or Meter 13
Variable or Meter 14 Name
Aggregation Type for Variable or Meter 14
Variable or Meter 15 Name
Aggregation Type for Variable or Meter 15
Variable or Meter 16 Name
Aggregation Type for Variable or Meter 16
Variable or Meter 17 Name
Aggregation Type for Variable or Meter 17
Variable or Meter 18 Name
Aggregation Type for Variable or Meter 18
Variable or Meter 19 Name
Aggregation Type for Variable or Meter 19
Variable or Meter 20 Name
Aggregation Type for Variable or Meter 20
Variable or Meter 21 Name
Aggregation Type for Variable or Meter 21
Variable or Meter 22 Name
Aggregation Type for Variable or Meter 22
Variable or Meter 23 Name
Aggregation Type for Variable or Meter 23
Variable or Meter 24 Name
Aggregation Type for Variable or Meter 24
Variable or Meter 25 Name
Aggregation Type for Variable or Meter 25


Report: COMFORT REPORT

For: BLOCK1:HEAVYMANUFACTURING HEAVYPEOPLE

Timestamp: 2014-12-03 08:09:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 ADAPTIVE MODEL 80% ACCEPTABILITY STATUS {HOURS NON-ZERO} [HOURS]ZONE THERMAL COMFORT ASHRAE 55 ADAPTIVE MODEL 90% ACCEPTABILITY STATUS {HOURS NON-ZERO} [HOURS]ZONE THERMAL COMFORT CEN 15251 ADAPTIVE MODEL CATEGORY I STATUS {HOURS NON-ZERO} [HOURS]ZONE THERMAL COMFORT CEN 15251 ADAPTIVE MODEL CATEGORY II STATUS {HOURS NON-ZERO} [HOURS]ZONE THERMAL COMFORT CEN 15251 ADAPTIVE MODEL CATEGORY III STATUS {HOURS NON-ZERO} [HOURS]ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]ZONE THERMAL COMFORT FANGER MODEL PMV {HOURS POSITIVE} [HOURS]ZONE THERMAL COMFORT FANGER MODEL PMV {HOURS NEGATIVE} [HOURS]ZONE THERMAL COMFORT FANGER MODEL PMV {HOURS ZERO} [HOURS]
January744.0744.0744.0744.0744.042.9131.3612.70.0
February672.0672.0648.0648.0648.040.6226.9445.10.0
March744.0744.0653.0656.8660.239.3265.4478.60.0
April189.1139.3360.5387.7423.535.0437.4282.60.0
May227.9164.2199.7250.9304.439.3625.8118.10.0
June213.9160.4138.5199.0261.751.6706.313.70.0
July282.6234.8226.7295.4344.960.3744.00.00.0
August266.9202.6174.0246.8317.060.9744.00.00.0
September230.4180.5169.4228.7302.238.1591.1128.90.0
October225.1161.3269.1312.2356.935.0460.3283.70.0
November720.0720.0633.6639.3645.434.7271.7448.40.0
December744.0744.0698.3700.7702.532.4156.1587.90.0
          
Annual Sum or Average5259.84867.14914.95309.35710.640.95360.33399.70.0
Minimum of Months189.1139.3138.5199.0261.732.4131.30.00.0
Maximum of Months744.0744.0744.0744.0744.060.9744.0612.70.0



Table of Contents

Report: ENERGY REPORT

For: Meter

Timestamp: 2014-12-03 08:09:25

Custom Monthly Report

DISTRICTCOOLING:HVAC [Invalid/Undefined]DISTRICTHEATING:HVAC [Invalid/Undefined]VENTILATION (SIMPLE):FANS:ELECTRICITY [Invalid/Undefined]INTERIORLIGHTS:ELECTRICITY [kWh]CARBON EQUIVALENT:FACILITY [kg]
January0.00.00.0292483.799845.4
February0.00.00.0264178.890183.0
March0.00.00.0292483.799845.4
April0.00.00.0283048.796624.6
May0.00.00.0292483.799845.4
June0.00.00.0283048.796624.6
July0.00.00.0292483.799845.4
August0.00.00.0292483.799845.4
September0.00.00.0283048.796624.6
October0.00.00.0292483.799845.4
November0.00.00.0283048.796624.6
December0.00.00.0292483.799845.4
      
Annual Sum or Average0.00.00.03443759.41175599.5
Minimum of Months0.00.00.0264178.890183.0
Maximum of Months0.00.00.0292483.799845.4





â??â??
Jeremiah D. Crossett
 
 | Senior Analyst  | LEED Green Associate 
â??â??
7411 SW Capitol Highway | Portland, OR 97219 
â??â??
 | Mobile 503-688-8951
  




On Wed, Dec 3, 2014 at 9:00 AM, m.waseemahmad@xxxxxxxxxxx [EnergyPlus_Support] <EnergyPlus_Support@xxxxxxxxxxxxxxx> wrote:
 

Hello All, 

Just wondering is there any way that EnergyPlus can output the number of hours the room air temperature was more than 25 [C] or number of people dissatisfied was more than 10%. It needs to be automatic, may be some C/C++ code?


The program needs to do some post processing to find the number of hours. 


Also, Can this be done by using EMS?


Your help will be really appreciated. 


Thanks

Kindest Regards

Waseem




__._,_.___

Posted by: Jeremiah Crossett <jcrossett@xxxxxxxxxxxxxxx>


Primary EnergyPlus support is found at:
http://energyplus.helpserve.com or send a message to energyplus-support@xxxxxxxx

The primary EnergyPlus web site is found at:
http://www.energyplus.gov

The group web site is:
http://groups.yahoo.com/group/EnergyPlus_Support/

Attachments are currently allowed but be mindful that not everyone has a high speed connection.  Limit attachments to small files.

EnergyPlus Documentation is searchable.  Open EPlusMainMenu.pdf under the Documentation link and press the "search" button.




Visit Your Group
Yahoo! Groups
PrivacyUnsubscribeTerms of Use

__,_._,___