[Equest-users] IDEC With DX

Amol Mehta amol.mehta at p2seng.com
Thu Dec 11 14:07:40 PST 2008


Hi 

 

I am trying model IDEC (Indirect Direct Evaporative Cooling) with DX and
Heat Pipe (Sensible HX). Has anyone modeled this before? Can you please help
me; my building energy performance seems to be not affected. Please see
figure below. If you don't see figure, here is the system description. The
supply stream has DX cooling coil, Direct Evaporative Cooler and a Supply
Fan. The Return Air Stream has Water Spray Nozzles with a Heat Pipe (Water
is Sprayed on pipe common to return and supply air stream for sensible heat
transfer), Mist Eliminator, Exhaust Fan, DX Condenser. I am having problem
to model this. 

 

Thank you in advance. 

 

 



 

 

Regards,

 

 

Amol Mehta | Mechanical Engineer | P2S Engineering, Inc.

T 562 497 2999 | F 562 497 2990 | M 858 354 6250

5000 East Spring Street, 8th Floor, Long Beach, CA  90815

-----Original Message-----
From: equest-users-bounces at lists.onebuilding.org
[mailto:equest-users-bounces at lists.onebuilding.org] On Behalf Of
equest-users-request at lists.onebuilding.org
Sent: Thursday, December 11, 2008 12:04 PM
To: equest-users at lists.onebuilding.org
Subject: Equest-users Digest, Vol 9, Issue 10

 

Send Equest-users mailing list submissions to

      equest-users at lists.onebuilding.org

 

To subscribe or unsubscribe via the World Wide Web, visit

      http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org

 

or, via email, send a message with subject or body 'help' to

      equest-users-request at lists.onebuilding.org

 

You can reach the person managing the list at

      equest-users-owner at lists.onebuilding.org

 

When replying, please edit your Subject line so it is more specific

than "Re: Contents of Equest-users digest..."

 

 

Today's Topics:

 

   1. Desiccants in eQuest (Karen Walkerman)

   2. Re: Multizone heating question (Karen Walkerman)

   3. Re: Multizone heating question (Daly, Matt)

   4. Re: Multizone heating question (James Hansen)

 

 

----------------------------------------------------------------------

 

Message: 1

Date: Thu, 11 Dec 2008 13:20:42 -0500

From: "Karen Walkerman" <kwalkerman at gmail.com>

Subject: [Equest-users] Desiccants in eQuest

To: "equest-users at lists.onebuilding.org"

      <equest-users at lists.onebuilding.org>

Message-ID:

      <69a9bc0a0812111020h478ccb4fj5eb35a1410766585 at mail.gmail.com>

Content-Type: text/plain; charset="iso-8859-1"

 

Hi All,

 

I'm wondering if anyone has any pearls of wisdom for setting up an add-on

desiccant in eQuest.  The program gives very little control as to how the

desiccant is used.  I am trying to model a desiccant dehumidification system

for a pool.  However, the add-on desiccant seems to only operate to

condition outdoor air.  Also, in the summary report "SUPL Evap/Desiccant

Cooling for..." there are some negative numbers under the "SENSIBLE COOLING

ENERGY (MBTU)" column.  This seems backwards to me.

 

Any input is appreciated!

 

Thanks,

 

--

Karen

-------------- next part --------------

An HTML attachment was scrubbed...

URL:
<http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachm
ents/20081211/ea3adb03/attachment.html>

 

------------------------------

 

Message: 2

Date: Thu, 11 Dec 2008 13:36:59 -0500

From: "Karen Walkerman" <kwalkerman at gmail.com>

Subject: Re: [Equest-users] Multizone heating question

To: "Marcus Eliason" <meliason at essexco.com>

Cc: equest-users at lists.onebuilding.org

Message-ID:

      <69a9bc0a0812111036i310d418ifd60bb24ac8e4138 at mail.gmail.com>

Content-Type: text/plain; charset="iso-8859-1"

 

I'm happy to look at your inp file, but I can't open it with eQuest.  My

initial guess is that you have a pilot on all summer, or that your boiler is

cycling at an inefficient part load ratio in response to small demands.

 

--

Karen

 

On Thu, Dec 11, 2008 at 1:25 PM, Marcus Eliason <meliason at essexco.com>wrote:

 

> 

> Hello,

> 

> I am modeling an existing building with multizone air handlers with
chilled

> water coils for cooling and hot water coils for heating.  The hot water is

> generated by a gas furnace.  I am seeing some discrepancies in my gas
usage

> from actual to the simulation.  In the actual building, the gas usage is

> only  high in the winter months (the building is in the south) and is next

> to nothing in summer months.  I have tried all the various methods of coil

> control under the "heating" tab and cannot get the simulation to reflect

> the

> real life usage.  Does anybody have any ideas on how to control the
heating

> better?  Representative files are attached.

> 

> Marcus Eliason

> 

> 

> _______________________________________________

> Equest-users mailing list

> http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org

> To unsubscribe from this mailing list send  a blank message to

> EQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG

> 

> 

-------------- next part --------------

An HTML attachment was scrubbed...

URL:
<http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachm
ents/20081211/431c2f79/attachment-0001.htm>

 

------------------------------

 

Message: 3

Date: Thu, 11 Dec 2008 10:56:35 -0800

From: "Daly, Matt" <Matt.Daly at wesd.org>

Subject: Re: [Equest-users] Multizone heating question

To: Marcus Eliason <meliason at essexco.com>

Cc: "equest-users at lists.onebuilding.org"

      <equest-users at lists.onebuilding.org>

Message-ID:

      <06D9FD985A42704BB0E8F483ACA3FE2E3EE49B49D0 at miranda.wesd.org>

Content-Type: text/plain; charset="us-ascii"

 

Yes, where is your weather file?

My guess is, your chilled air stream needs to be mixed with heated air to
raise it to a proper zone temperature.

 

 

Matt Daly * Project Manager * Willamette ESD

2611 Pringle Road SE * Salem, OR 97302

503-385-4693 * fax 503-540-2959

matt.daly at wesd.org<mailto:matt.daly at wesd.org>

 

From: equest-users-bounces at lists.onebuilding.org
[mailto:equest-users-bounces at lists.onebuilding.org] On Behalf Of Karen
Walkerman

Sent: Thursday, December 11, 2008 10:37 AM

To: Marcus Eliason

Cc: equest-users at lists.onebuilding.org

Subject: Re: [Equest-users] Multizone heating question

 

I'm happy to look at your inp file, but I can't open it with eQuest.  My
initial guess is that you have a pilot on all summer, or that your boiler is
cycling at an inefficient part load ratio in response to small demands.

 

--

Karen

On Thu, Dec 11, 2008 at 1:25 PM, Marcus Eliason
<meliason at essexco.com<mailto:meliason at essexco.com>> wrote:

 

Hello,

 

I am modeling an existing building with multizone air handlers with chilled

water coils for cooling and hot water coils for heating.  The hot water is

generated by a gas furnace.  I am seeing some discrepancies in my gas usage

from actual to the simulation.  In the actual building, the gas usage is

only  high in the winter months (the building is in the south) and is next

to nothing in summer months.  I have tried all the various methods of coil

control under the "heating" tab and cannot get the simulation to reflect the

real life usage.  Does anybody have any ideas on how to control the heating

better?  Representative files are attached.

 

Marcus Eliason

 

 

_______________________________________________

Equest-users mailing list

http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org

To unsubscribe from this mailing list send  a blank message to
EQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG<mailto:EQUEST-USERS-UNSUBSCRIBE at ONE
BUILDING.ORG>

 

-------------- next part --------------

An HTML attachment was scrubbed...

URL:
<http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachm
ents/20081211/22c6a1df/attachment-0001.htm>

 

------------------------------

 

Message: 4

Date: Thu, 11 Dec 2008 14:01:36 -0500

From: "James Hansen" <JHANSEN at ghtltd.com>

Subject: Re: [Equest-users] Multizone heating question

To: "Daly, Matt" <Matt.Daly at wesd.org>,"Marcus Eliason"

      <meliason at essexco.com>

Cc: equest-users at lists.onebuilding.org

Message-ID:

 
<25F2BDB6656B8F40A1289ED906D6B5CF038E1367 at EXCHANGE1.cadd_group.ghtltd.com>

      

Content-Type: text/plain; charset="us-ascii"

 

I looked at your .inp file - with a multizone system, you have the

heating coil of the dual duct scenario running all the time - it doesn't

look like you can set the minimum flow rate thru this coil to 0, which

means theoretically there is always a heating load, and perhaps the

boiler is running constantly during FAN ON conditions.  Just a guess.

Also, you have the heating and cooling setpoints at the same temp (68

degrees).  From my experience, you don't want to do this...it may cause

unexpected problems, especially when you are talking about multiple

thermostats controlling a complicated dual duct system.

 

 

 

GHT Limited

James Hansen, PE, LEED AP

 

Senior Associate

 

1010 N. Glebe Rd, Suite 200

 

Arlington, VA  22201-4749

 

703-338-5754 (Cell)

 

703-243-1200 (Office)

 

703-276-1376 (Fax)

 

www.ghtltd.com <http://www.ghtltd.com/> 

 

 

 

From: equest-users-bounces at lists.onebuilding.org

[mailto:equest-users-bounces at lists.onebuilding.org] On Behalf Of Daly,

Matt

Sent: Thursday, December 11, 2008 1:57 PM

To: Marcus Eliason

Cc: equest-users at lists.onebuilding.org

Subject: Re: [Equest-users] Multizone heating question

 

 

 

Yes, where is your weather file?

 

My guess is, your chilled air stream needs to be mixed with heated air

to raise it to a proper zone temperature.

 

 

 

 

 

Matt Daly * Project Manager * Willamette ESD 

2611 Pringle Road SE * Salem, OR 97302 

503-385-4693 * fax 503-540-2959

 

matt.daly at wesd.org <mailto:matt.daly at wesd.org>  

 

 

 

From: equest-users-bounces at lists.onebuilding.org

[mailto:equest-users-bounces at lists.onebuilding.org] On Behalf Of Karen

Walkerman

Sent: Thursday, December 11, 2008 10:37 AM

To: Marcus Eliason

Cc: equest-users at lists.onebuilding.org

Subject: Re: [Equest-users] Multizone heating question

 

 

 

I'm happy to look at your inp file, but I can't open it with eQuest.  My

initial guess is that you have a pilot on all summer, or that your

boiler is cycling at an inefficient part load ratio in response to small

demands.

 

--

Karen

 

On Thu, Dec 11, 2008 at 1:25 PM, Marcus Eliason <meliason at essexco.com>

wrote:

 

 

Hello,

 

I am modeling an existing building with multizone air handlers with

chilled

water coils for cooling and hot water coils for heating.  The hot water

is

generated by a gas furnace.  I am seeing some discrepancies in my gas

usage

from actual to the simulation.  In the actual building, the gas usage is

only  high in the winter months (the building is in the south) and is

next

to nothing in summer months.  I have tried all the various methods of

coil

control under the "heating" tab and cannot get the simulation to reflect

the

real life usage.  Does anybody have any ideas on how to control the

heating

better?  Representative files are attached.

 

Marcus Eliason

 

 

_______________________________________________

Equest-users mailing list

http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org

To unsubscribe from this mailing list send  a blank message to

EQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG

 

 

 

 

The information contained in this communication is confidential, may be
privileged, and is intended only for the use of the addressee.  It is the
property of GHT Limited.  Unauthorized use, disclosure or copying of this
communication or any part thereof is strictly prohibited and may be
unlawful.  If you have received this communication in error, please notify
me immediately by return e-mail or by e-mail to ght at ghtltd.com, and destroy
this communication and all copies thereof, including all attachments.  Thank
you.

 

 

 

-------------- next part --------------

An HTML attachment was scrubbed...

URL:
<http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachm
ents/20081211/80b8e419/attachment-0001.htm>

 

------------------------------

 

_______________________________________________

Equest-users mailing list

Equest-users at lists.onebuilding.org

http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org

 

 

End of Equest-users Digest, Vol 9, Issue 10

*******************************************

-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20081211/26f17907/attachment.htm>
-------------- next part --------------
A non-text attachment was scrubbed...
Name: not available
Type: image/gif
Size: 96338 bytes
Desc: not available
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20081211/26f17907/attachment.gif>
-------------- next part --------------
A non-text attachment was scrubbed...
Name: not available
Type: application/octet-stream
Size: 111234 bytes
Desc: not available
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20081211/26f17907/attachment.obj>


More information about the Equest-users mailing list