Dear Zhou,

OA can be inputed under the zone, which is conditioned by PTAC.

Referred to *<DOE2.2 Volume 3: Topics>*, Section AIRSIDE HVAC, SYSTEM TYPE =
PTAC, page 272, you can see that OA control is not under AC system, and on
page 273 and 274 there is an example input for this system: *OA control is
under zone control*.

After setting, you can output OA hourly data to check it works or not.

Regards,

Grammy

On Sat, Dec 11, 2010 at 11:27 PM, zhiren zhou <zhouzr at cabr-sh.com> wrote:

> Dear eQUESTers
>
>        I am doing LEED-CS energy rating simulation. Part of the project is
> residential type (hotel) and the HVAC system for baseline is PTAC while the
> proposed system is FCU+DOAs. The Appendix G doesn’t  tell  us to create
> the PTAC baseline system with DOAS. But the question is how to set the OA
> value to PTAC system in  eQUEST?  I think I should set the OA value in the
> interface below, but how? Has anyone performed the PTAC simulation and Can
> you tell me the details or can you give me an example you did?
>
>          Thanks a lot!
>
>
>
>                                                         Yours Zhiren Zhou
>
>
>
> [image: cid:image001.png at 01CB991B.D66A79A0]
>
> _______________________________________________
> Equest-users mailing list
> http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org
> To unsubscribe from this mailing list send  a blank message to
> EQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG
>
>
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20101212/522fbec4/attachment-0002.htm>


More information about the Equest-users mailing list