[Equest-users] activity area allocation and zone group definitions
Pasha Korber-Gonzalez
pasha.pkconsulting at gmail.com
Wed Jul 7 09:46:54 PDT 2010
Hi Paul,
These screens were an anomolie (sp?) to me until just this year thanks to a
younger fellow simulator who uses them quite efficiently. In fact, I always
skipped out of the wizard when it came to these screens until I took the
time to learn how to readjust & reallocate the % space inputs on these
screens. After learning to do this I now spend less time on the back-end
(ddedit mode) adjusting my HVAC system assignments... Yay!
Here's my attempt to explain what I've learned. I'll call out my colleague
Dan W. for help on this one if I mess it up...
Screen 13 is your % space based on the WHOLE BUILDING floor area. When you
move to screen 14 this is where you actually assign HVAC systems to your
zone groups. A zone group is a group of zones that can be assigned to the
same HVAC system. (NOTE: at this point you will want to have created your
basic HVAC systems types already in the wizard. This was a backward step
for me at first, but it works for when you switch to ddedit mode.)
So in screen 14 the % space for zone groups is based on the total floor
area of all the zones you want to group together. (at this point you should
also have a basic take off of floor area for your thermal zones.) Now after
you have "grouped" your zones that you want together you need to revise the
% space numbers in the top of the screen. (I've included a screen shot of
one of my models where I used the zone groups.) Note how I have zeroed-out
some of the % space input for other zones that I have not grouped into my
specific group I'm calling "Conference Center." With the revised % space
numbers make sure that they add up to 100%.
So to answer your question, when you use Screen 14 correctly these inputs
will override screen 13. If I should clarify anything better let me know.
Pasha
On Wed, Jul 7, 2010 at 9:45 AM, Paul Brooks <equestpaul at yahoo.com> wrote:
> Does anyone have any idea which of screen 13 or 14 in the DD wizard
> overides the other? I am using zone group definitions to give dtail on how
> individual zone space is allocated (screen 14 of 25), but that does not seem
> to affect the activites area allocation, (screen 13 of 25).
>
> Anone have any thoughts or experience to share?
>
> Thanks!
>
>
> _______________________________________________
> Equest-users mailing list
> http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org
> To unsubscribe from this mailing list send a blank message to
> EQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG
>
>
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20100707/66ede4be/attachment-0001.htm>
-------------- next part --------------
A non-text attachment was scrubbed...
Name: zone groups.docx
Type: application/vnd.openxmlformats-officedocument.wordprocessingml.document
Size: 178932 bytes
Desc: not available
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20100707/66ede4be/attachment-0001.bin>
More information about the Equest-users
mailing list