[Equest-users] Fan Motor Efficiency Change

John Aulbach jra_sac at yahoo.com
Wed Jul 28 11:11:34 PDT 2010


Thank you, Jeremy. By "plug and chug", that seemed to be the Parameter that 
changed in running a test building through Standard, High, and Premium 
Efficiency.

Wouldn't it be nice if some of this stuff was discussed more in the Manuals ??

John




________________________________
From: Jeremy McClanathan <jmcclanathan at CDiengineers.com>
To: John Aulbach <jra_sac at yahoo.com>; Demba Ndiaye <Demba.Ndiaye at setty.com>; 
"equest-users at lists.onebuilding.org" <equest-users at lists.onebuilding.org>
Sent: Wed, July 28, 2010 10:56:45 AM
Subject: RE: [Equest-users] Fan Motor Efficiency Change

 
I account for motor eff by changing the total eff, where total eff = motor eff * 
mech eff.  I believe the keyword for total eff in the inp file is SUPPLY-EFF for 
supply fans.
 
___________________________________________
 
Jeremy McClanathan, LEED® AP
CDi ENGINEERS
4200 194th St SW, Ste 200, Lynnwood, WA 98036
P 425-672-1071 | F 425-778-8769 
PPlease consider the environment before printing this email.
 
 
 
From:John Aulbach [mailto:jra_sac at yahoo.com] 
Sent: Wednesday, July 28, 2010 10:51 AM
To: Demba Ndiaye; equest-users at lists.onebuilding.org
Subject: Re: [Equest-users] Fan Motor Efficiency Change
 
Thank you, Demba.
 
But this is for a PUMP. Not a FAN.
 
John
 

________________________________

From:Demba Ndiaye <Demba.Ndiaye at setty.com>
To: John Aulbach <jra_sac at yahoo.com>; "equest-users at lists.onebuilding.org" 
<equest-users at lists.onebuilding.org>
Sent: Wed, July 28, 2010 10:39:34 AM
Subject: RE: [Equest-users] Fan Motor Efficiency Change
John, 
 
In the INP, it is the “MOTOR-CLASS” input. You see in the INP something like:
 
FLOW             = 300
                NUMBER           = 1
                HEAD             = 80
                MECH-EFF         = 0.776
                MOTOR-CLASS      = HI-EFF
                CAP-CTRL         = ONE-SPEED-PUMP
 
_____________
Demba NDIAYE
 
From:equest-users-bounces at lists.onebuilding.org 
[mailto:equest-users-bounces at lists.onebuilding.org] On Behalf Of John Aulbach
Sent: Wednesday, July 28, 2010 12:34 PM
To: equest-users at lists.onebuilding.org
Subject: [Equest-users] Fan Motor Efficiency Change
 
I should know this one, but draw a blank.
 
The Wizard asks if you want Standard, Hi Efficiency, or Premium Efficiency 
motors for your fan system.
 
How do those show up in the .INP file? That will give me a clue as to what 
Parameters to modify for changing to PE motors.
 
Thanks.
 
John R. Aulbach, PE, CEM
Senior Energy Engineer

________________________________

PartnerEnergy
1990 E. Grand Avenue, El Segundo, CA 90245
W: 888-826-1216, X254| D: 310-765-7295 | F: 310-817-2745
www.ptrenergy.com| jaulbach at ptrenergy.com
 
 
 
 
This email message, including any attachments, is for the sole use of the 
intended recipient and may contain confidential, proprietary, and/or privileged 
information, as well as content subject to copyright and other intellectual 
laws.  If you are not the intended recipient, you may not disclose, use, copy, 
or distribute the email message or its attachments.  If you believe you have 
received this email message in error, please contact the sender by reply email, 
immediately delete this email and destroy copies.


      
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20100728/d719805e/attachment-0001.htm>


More information about the Equest-users mailing list