It is for heating values actually. But the same explanation holds for heating 
because the loads in LS-D are based on maintaining an assumed constant indoor 
temperature, calculated for 24x7 loads. On the other hand, the values in SS-D 
include outside ventilation air, duct loss/gain, economizer effects etc. 

By the way, for the people who haven't discovered yet, there is a report called 
Detailed Simulation Reports Summary under your equest data folder 
(Tutorials>DetailedUI) which is very useful to understand what is presented in 
the detailed simulation report.

Thanks everyone for answers.

Best Regards
Sinan Senel




________________________________
From: "Haddad, Kamel" <Kamel.Haddad at NRCan-RNCan.gc.ca>
To: sinan senel <msinansenel at yahoo.com>; equest-users at lists.onebuilding.org
Sent: Thu, July 15, 2010 12:48:04 AM
Subject: RE: [Equest-users] LS-D Building Monthly Loads Summary

Is this for heating or cooling?

If cooling it could then be the effect of an economizer or natural ventilation 
which basically amounts to free cooling and help displace some of the load.

Kamel Haddad

________________________________

From: equest-users-bounces at lists.onebuilding.org on behalf of sinan senel
Sent: Wed 14/07/2010 6:31 PM
To: equest-users at lists.onebuilding.org
Subject: [Equest-users] LS-D Building Monthly Loads Summary


Dear all,


I have quite high values from simulation report under LS-D building monthly 
loads summary compared to values in SS-D Building HVAC Load Summary. Can anybody 
predict what might be the reason? And what is exactly presented in LS-D report?

Thanks in advance.

Regards
Sinan Senel


      