[Equest-users] pnuematic -> DDC controls
Paul Diglio
paul.diglio at sbcglobal.net
Mon Nov 22 10:19:58 PST 2010
Vincent:
I have developed many projects that include the conversion from pneumatic to
electronic actuated valves and dampers.
I investigate the existing pneumatic control system to document valve and damper
overlap and other calibration errors and develop an Excel spreadsheet to
calculate the savings. I often used Hobo dataloggers to track the existing
temperature and reset errors.
An important consideration is if the existing system employs discharge air
temperature reset and if this reset is based on OA or high-low space
temperature. The more complex pneumatic systems of yesteryear can do either as
well as static pressure reset and even comparative OA-RA enthalpy.
A DDC system might not save much energy if replacing a well maintained and
calibrated pneumatic control system. In addition, if the DDC programmer does
not calibrate the PID loops correctly, the DDC system might actually use more
energy.
Commissioning helps identify and correct this problem.
I don't think that I would try to calculate these savings using eQuest. Excel
is a better tool for this function.
Good luck,
Paul Diglio
________________________________
From: "Priolo, Vincent" <Vincent.Priolo at trane.com>
To: "equest-users at lists.onebuilding.org" <equest-users at lists.onebuilding.org>
Sent: Mon, November 22, 2010 1:03:53 PM
Subject: Re: [Equest-users] pnuematic -> DDC controls
Dear all,
New user here working on modeling VAV pneumatic to DDC conversion for energy
savings. Looking to model chilled water reset, hot water reset, pressure
reset, increased VAV response, and energy savings from compressor. Looks like
model must be done in Design Development Wizard.
Any advice?
Vince Priolo
Energy Solutions Engineer
Southern CaliforniaTrane
Cell - 805-550-4298
Direct - 626-435-1187
vincent.priolo at trane.com
________________________________
From:equest-users-bounces at lists.onebuilding.org
[mailto:equest-users-bounces at lists.onebuilding.org] On Behalf Of Praveen Jain
Sent: Sunday, November 21, 2010 11:35 PM
To: equest-users at lists.onebuilding.org
Subject: [Equest-users] Relative Humidity in Unco
Dear All
Is it possible to know Relative Humidity in unconditioned zone of eQUEST ?
--
With Thanks and Regards,
Praveen K. Jain
Roorkee
________________________________
The information contained in this message is privileged and intended only for
the recipients named. If the reader is not a representative of the intended
recipient, any review, dissemination or copying of this message or the
information it contains is prohibited. If you have received this message in
error, please immediately notify the sender, and delete the original message and
attachments.
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20101122/b6ce9c92/attachment-0002.htm>
More information about the Equest-users
mailing list