The formula for G3.1.2.9 inlcudes the fan power for both the supply and return fans.
The baseline model should usually be modeled as per the design i.e. if there are return fans then model them. However if for some reason you would like to calculate the supply and return power together and enter it as a supply fan you can do so also. You shouldn’t ignore the return.
Christie Rimes, LEED BD+C
Designer
WSP ▪ FLACK + KURTZ
405 Howard Street, Suite 500
San Francisco, CA 94105
Direct: 415.402.2727 | Main: 415.398.3833
www.wspfk.com <http://www.wspfk.com/>
Ensuring that today’s built environment preserves the natural environment in which we all live.
We are WSP. United by our difference.
WSP is one of the world’s fastest-growing design, engineering and management consultancies. Specializing in property, transport and environmental projects, we work with clients to create built and natural environments for the future.
CONFIDENTIAL
This e-mail is confidential to the named recipient. If you have received a copy in error, please destroy it. You may not use or disclose the contents of this e-mail to anyone, nor take copies of it. The only copies permitted are (1) by the named recipient and (2) for the purposes of completing successful electronic transmission to the named recipient and then only on the condition that these copies, with this notice attached, are kept confidential until destruction
From: equest-users-bounces at lists.onebuilding.org [mailto:equest-users-bounces at lists.onebuilding.org] On Behalf Of Jeff Ross-Bain
Sent: Monday, April 18, 2011 12:47 PM
To: equest-users at lists.onebuilding.org
Subject: [Equest-users] ASHRAE G3.1.2.9 Supply Fan Power
Hi All,
If an HVAC system comprises both a supply and return fan, and the formula for G3.1.2.9 is used, does the result, Pfan, represent ALL of the fan power for that system including supply and return? If so, should the baseline model only depict the supply fan values (CFM, kW/CFM, etc.) and ignore the return?
Many thanks,
Jeffrey G Ross-Bain, PE, LEED AP, BEMP
404-228-2893 office
404-408-2577 mobile
www.rbgb.com
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20110418/20fda07c/attachment-0002.htm>
More information about the Equest-users
mailing list