[Equest-users] Return Fans
Bruce Easterbrook
bruce5 at bellnet.ca
Mon Oct 29 10:26:17 PDT 2012
You need to exhaust the 1500 CFM. If you exhaust 1200 eQuest will
assume there is 300 CFM of return air. Your model is a box.
_Everything_ going in or out must balance. If you don't do it eQuest will.
Bruce Easterbrook P.Eng.
Abode Engineering
On 29/10/2012 12:36 PM, Ömer Moltay wrote:
> Dear All,
>
> I am trying to model a system with 1500 CFM system supply but no
> return, all of the flow will be exhausted from the zones. Looking at
> hourly reports, I can never get the return flow to be zero, eQuest
> will always add exhaust and return and make my system supply 3000 CFM.
> How does one zero the return flow?
>
> Thanks,
>
> Omer Moltay