[Equest-users] Simulation Run Terminates when generating reports
Sami, Vikram
Vikram.Sami at perkinswill.com
Fri Feb 1 12:20:13 PST 2013
I would check your coil temps, and also make sure your supply air temp is sufficiently higher than your coil temp.
Vikram Sami, LEED AP BD+C
Sustainable Design Analyst
1315 Peachtree St. NE, Atlanta, GA 30309
t: 404-443-7462 f: 404.892.5823 e: vikram.sami at perkinswill.com www.perkinswill.com<http://www.perkinswill.com/>
Perkins+Will. Ideas + buildings that honor the broader goals of society
From: equest-users-bounces at lists.onebuilding.org [mailto:equest-users-bounces at lists.onebuilding.org] On Behalf Of Mike Raiva
Sent: Friday, February 01, 2013 1:08 PM
To: John Aulbach
Cc: equest-users at lists.onebuilding.org
Subject: Re: [Equest-users] Simulation Run Terminates when generating reports
Here is the error that I getting.
***ERROR***********************************************************************
In EL1 Sys7 (VAVS) (G.WSW16) , cooling coil leaving temperature must
be at least 6F higher than entering water temp.
MICHAEL RAIVA, P.Eng., LEED® AP
Mechanical
Williams Engineering Canada Inc.
T: 778.484.2983 F: 778.484.3901
W: williamsengineering.com<http://www.williamsengineering.com>
Engage. Innovate. Inspire.
Please consider the environment before printing this email.
Email Transmission Policy<http://www.williamsengineering.com/legal>
From: John Aulbach [mailto:jra_sac at yahoo.com]
Sent: Friday, February 01, 2013 9:59 AM
To: Mike Raiva
Subject: Re: [Equest-users] Simulation Run Terminates when generating reports
Sir:
Have you tried hitting the Detail Output button? Many times, it will list your errors.
John R. Aulbach, PE
________________________________
From: Mike Raiva <mraiva at williamsengineering.com<mailto:mraiva at williamsengineering.com>>
To: "equest-users at lists.onebuilding.org<mailto:equest-users at lists.onebuilding.org>" <equest-users at lists.onebuilding.org<mailto:equest-users at lists.onebuilding.org>>
Sent: Friday, February 1, 2013 9:54 AM
Subject: [Equest-users] Simulation Run Terminates when generating reports
I am getting my model to simulate performance. However, it’s terminating when producing Summary and Verification reports with the following error shown below.
Is there a way to trace where the error is?
Thank you.
[cid:image001.png at 01CE008F.A1F870E0]
MICHAEL RAIVA, P.Eng., LEED® AP
Mechanical
Williams Engineering Canada Inc.
T: 778.484.2983 F: 778.484.3901
W: williamsengineering.com<http://www.williamsengineering.com/>
Engage. Innovate. Inspire.
Please consider the environment before printing this email.
Email Transmission Policy<http://www.williamsengineering.com/legal>
_______________________________________________
Equest-users mailing list
http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org
To unsubscribe from this mailing list send a blank message to EQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG<mailto:EQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG>
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20130201/dc4ba1e3/attachment-0002.htm>
-------------- next part --------------
A non-text attachment was scrubbed...
Name: image001.png
Type: image/png
Size: 16595 bytes
Desc: image001.png
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20130201/dc4ba1e3/attachment-0002.png>
More information about the Equest-users
mailing list