[Equest-users] Relative Humdity
Joe Huang
yjhuang at whiteboxtechnologies.com
Wed Apr 9 12:37:56 PDT 2014
Do you mean the relative humidity on the weather file?
That would require changing the weather file, but that's not a task for the timid because:
1) the weather file is in a binary format that you can't read, so you'd have to convert it
to ASCII, make the changes, and convert that back. There are Fortran programs for doing
that, though.
2) RH is a derived value that's not in the weather file. You would have to change several
weather elements and make sure that they're all consistent - absolute humidity, wet bulb,
and enthalpy.
Joe
Joe Huang
White Box Technologies, Inc.
346 Rheem Blvd., Suite 108D
Moraga CA 94556
yjhuang at whiteboxtechnologies.com
http://weather.whiteboxtechnologies.com for simulation-ready weather data
(o) (925)388-0265
(c) (510)928-2683
"building energy simulations at your fingertips"
On 4/9/2014 12:29 PM, Fakeha Sehar wrote:
> How can relative humidity be changed in eQuest?
>
>
> _______________________________________________
> Equest-users mailing list
> http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org
> To unsubscribe from this mailing list send a blank message to EQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG
-------------- next part --------------