[TRNSYS-users] Help needed with Type-56 thermal mass thermal time constatnt problems
Joynal Abedin
J.Abedin at lboro.ac.uk
Sun Mar 23 02:35:57 PDT 2014
Hi,
I’m simulating a domestic building using Type-56 with three thermal zones. All the building fabrics such as the external walls are massive with the correctly defined conductivity, heat capacity and density. However, when I simulate the building the thermal response of the rooms appear to have very low thermal time constant i.e. it changes very rapidly and it seems that the massive walls with specific heat capacity are not having any heat storage impact. The capacity value in the Air Zone Regime gets automatically to 1.2 times the volume of the room. If I manually increase this value the thermal time constant does increase, but should I be increasing this value? The main problem I think is that the thermally massive walls are not having any thermal mass effects on the temperature response of the rooms. What am I doing wrong? Why is the heat capacity of the air zone set to 1.2 times the zone volume? One building in TRNSYS17 Example projects have this set to 3 times the Volume.
If anybody as any ideas or suggestions please please email me. Your help will be very much appreciated.
Thanking you in advance.
Kind regards,
Joynal Abedin.
Loughborough University, UK.
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/trnsys-users-onebuilding.org/attachments/20140323/93aa9f14/attachment-0001.htm>
More information about the TRNSYS-users
mailing list