[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

RE: [EnergyPlus_Support] About exterior surface convection coefficient algorithms in EP





I don’t know TAS and IES but is sounds like they are old fashioned models whose “convection coefficient” actually combines convection and thermal radiation into a single coefficient.  That is what E+’s “simple” model does. 

 

Combining convection and radiation into a single coefficient is a simplification that many older/simpler programs make to model heat flows.  But it is a poor approach when calculating surface temperatures.  

 


From: EnergyPlus_Support@xxxxxxxxxxxxxxx [mailto:EnergyPlus_Support@xxxxxxxxxxxxxxx] On Behalf Of hvacgeshen516
Sent: Tuesday, June 02, 2009 12:57 AM
To: EnergyPlus_Support@xxxxxxxxxxxxxxx
Subject: [EnergyPlus_Support] About exterior surface convection coefficient algorithms in EP

 




If the algorithms except simple are chosen, the wind-driven convection coefficient will be much smaller than algorithms implemented by other software like TAS or IES.

Is there any comments on this?

Thanks and Regards
Xiangjing =)



__._,_.___


The primary EnergyPlus web site is found at:
http://www.energyplus.gov

The group web site is:
http://groups.yahoo.com/group/EnergyPlus_Support/

Attachments are not allowed -- please post any files to the appropriate folder in the Files area of the Support Web Site.

EnergyPlus Documentation is searchable.  Open EPlusMainMenu.pdf under the Documentation link and press the "search" button.




Your email settings: Individual Email|Traditional
Change settings via the Web (Yahoo! ID required)
Change settings via email: Switch delivery to Daily Digest | Switch to Fully Featured
Visit Your Group | Yahoo! Groups Terms of Use | Unsubscribe

__,_._,___