[Equest-users] (no subject)
Dan Jestico
djestico at hilsonmoran.com
Wed Jun 17 06:37:55 PDT 2009
Hi Kimberley,
I have recently dealt with this exact same problem. You need to move the
dummy zone system and zones in the .inp file you attached to the top of
the HVAC systems/zones list.
Hope this helps.
Dan.
________________________________
From: equest-users-bounces at lists.onebuilding.org
[mailto:equest-users-bounces at lists.onebuilding.org] On Behalf Of
Kimberly Killian
Sent: 17 June 2009 14:29
To: equest-users at lists.onebuilding.org
Subject: [Equest-users] (no subject)
Good afternoon,
I am trying to add a mixed air unit onto a four-pipe fan coil system
through the use of a dummy zone, from which my real zones will get their
outside air. I get the following error:
"EL1 Sys1 (FC) (G.E16) defined before its OA-FROM-SYSTEM. This will
cause incorrect OA temperature calculation. Move this SYSTEM to be
defined before its OA-FROM-SYSTEM in the project BDL input file."
The catch is that there is no BDL file, as the simulation aborts before
it is complete. Is there another way to define the MAU before the Fan
Coil System. I have searched a number of terms in the user's group and
there are many questions related to this topic, but I can't find any
answers. Any help would be appreciated.
Regards,
Kimberly Killian
Northern Architects, Inc.
207 King Street Suite 3
Burlington VT 05401
T: 802-658-1953
F: 802-658-2975
______________________________________________________________________
This email has been scanned by the MessageLabs Email Security System.
For more information please visit http://www.messagelabs.com/email
______________________________________________________________________
______________________________________________________________________
This email has been scanned by the MessageLabs Email Security System.
For more information please visit http://www.messagelabs.com/email
______________________________________________________________________
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20090617/e5d1b858/attachment-0002.htm>
More information about the Equest-users
mailing list