Thanks, could you please tell me why I cannot use water loop heat pump type? I don't want to lose the heat exchange between the heat pump through the water loop. Some HPs could be doing heating meanwhile other are doing cooling. If I model the system like air handle with a HP as heating source and water cooled condenser , I am not sure that this present the interaction between the HPs.
Hector Lampra, P. Eng, LEED AP, CEM
From: Bishop, Bill [mailto:wbishop at pathfinder-ea.com]
Sent: November-14-11 3:51 PM
To: Hector Lamprea; equest-users at lists.onebuilding.org
Subject: RE: [Equest-users] Water loop heat Pumps
Hector,
You can simulate a water-to-air heat pump using the PSZ, PVVT or PVAVS system types by selecting HEAT-PUMP as the HEAT-SOURCE and selecting WATER-COOLED as the cooling CONDENSER-TYPE.
Regards,
Bill
[cid:image001.png at 01CCA2E5.F99F29F0]
From: equest-users-bounces at lists.onebuilding.org<mailto:equest-users-bounces at lists.onebuilding.org> [mailto:equest-users-bounces at lists.onebuilding.org]<mailto:[mailto:equest-users-bounces at lists.onebuilding.org]> On Behalf Of Hector Lamprea
Sent: Monday, November 14, 2011 2:16 PM
To: equest-users at lists.onebuilding.org<mailto:equest-users at lists.onebuilding.org>
Subject: [Equest-users] Water loop heat Pumps
Could anybody help me this: I have a 7 stories building, that is heated through a water loop heat pump. I could not specify the outside air , or the heat recovery in this type of system. These areas are grey out.
thanks
Hector Lamprea, P, Eng. LEED AP. C.E.M PO Box 6626
Intermediate Mechanical Engineer Saint John, NB E2L 4S1
www.fundyeng.com<http://www.fundyeng.com>
[Description: image001]
Serving Our Clients' Needs First Tel: 506.635.1566
Dir 506.674.9413
Cell: 506.651.5350
Fax: 506.635.0206
This communication and its attachments are confidential and may be privileged.
If you are not the intended recipient, please immediately notify the sender and then
delete this communication and its attachments without reading it or forwarding it.
Many thanks.
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20111114/47f1672f/attachment-0002.htm>
-------------- next part --------------
A non-text attachment was scrubbed...
Name: image001.png
Type: image/png
Size: 21646 bytes
Desc: image001.png
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20111114/47f1672f/attachment-0002.png>
-------------- next part --------------
A non-text attachment was scrubbed...
Name: image002.jpg
Type: image/jpeg
Size: 2961 bytes
Desc: image002.jpg
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20111114/47f1672f/attachment-0002.jpg>
More information about the Equest-users
mailing list