DOE-2 modifies the COOL-EIR using several curves COOL-EIR-FT as a function of outdoor 
conditions and COOL-EIR-FPLR as a function of the Part Load Ratio. I suppose you could set 
those to be constant. Another way would be to just take the Cooling Load from the SS-D 
report and divide that by your constant COP. But my question would be, why do you want to 
do that ?

Joe