[Equest-users] HEAT-EIR-FT for heat pumps with water cooled condensers?
Anthony Hardman
anthony at greenengineer.com
Mon Apr 14 09:01:21 PDT 2014
Entering indoor wet bulb and entering (condenser) water temperature I
believe.
Anthony Hardman, PE, LEED AP BD+C
Senior Building Performance Analyst
The Green Engineer, Inc.
Sustainable Design Consulting
54 Junction Square Dr.
Concord, MA 01742
O: (978) 610-2801
C: (720) 840-7862
The Green Engineer, Inc. is a Certified B Corporation
From: Brian Fountain [mailto:bfountain at greensim.com]
Sent: Sunday, April 13, 2014 1:21 PM
To: equest-users at lists.onebuilding.org
Subject: [Equest-users] HEAT-EIR-FT for heat pumps with water cooled
condensers?
I am modelling a building with distributed water loop heat pumps. I am
looking at the electricity used for space heating (the compressor energy in
heating mode). This depends on a part load curve HEAT-EIR-FT which is a
function of two temperatures. Based on the DOE2 documentation, it is not
clear to me which two temperatures this curve is using to modify the
compressor energy for a water-cooled heat pump.
For an air-cooled heat pump, the curve is a function of entering dry-bulb
temperature and outdoor dry-bulb temperature. I want to know what the X and
Y values are for a water-cooled heat pump.
Can anyone provide any clarification on this?
Many thanks.
Brian