[Equest-users] Section 179D Question
Steve Jacobs
sjacobseng at gmail.com
Fri Apr 25 08:05:49 PDT 2014
I agree that it is explicit on what version 90.1-2001 to use and what
addendum. But there is no such clarification on the version of Appendix G.
- Steve
On 4/25/2014 8:51 AM, Paul Riemer wrote:
>
> The legislation clearly states ASHRAE 90.1-2001 as in effect on April
> 2, 2003 and lists which addenda that includes. The NREL published
> 'Guidelines' document says the same thing.
>
> It combines tax law, accounting, building design, and energy modeling
> so yes there are lots of 'hiccups' out there.
>
> **
>
> *Paul Riemer, PE, LEED AP BD+C*
>
> *DUNHAM*
>
> *From:*equest-users-bounces at lists.onebuilding.org
> [mailto:equest-users-bounces at lists.onebuilding.org] *On Behalf Of
> *Steve Jacobs
> *Sent:* Friday, April 25, 2014 9:32 AM
> *To:* Busby, Aaron; Tom Mickley; equest-users at lists.onebuilding.org
> *Subject:* Re: [Equest-users] Section 179D Question
>
> I'm not aware of anything says we can or can't use addendum to
> Appendix G. It is certainly frustrating not having anywhere to take
> questions. The inability for modelers to seek clarifications means
> that the community is probably taking a lot of different approaches to
> the incentive.
>
>
>
> On 4/25/2014 6:56 AM, Busby, Aaron wrote:
>
> ASHRAE 90.1 has several addendums now that have added system
> types, just for warehouse type spaces where they are heated only.
> Look for Addenda DN, system types 10 and 11.
>
> */Aaron Busby, PE, LEED AP/*
>
> Tel: 770.563.1522
> Cell: 678.642.7549
>
> *From:* equest-users-bounces at lists.onebuilding.org
> <mailto:equest-users-bounces at lists.onebuilding.org>
> [mailto:equest-users-bounces at lists.onebuilding.org] *On Behalf Of
> *Tom Mickley
> *Sent:* Friday, April 25, 2014 8:38 AM
> *To:* equest-users at lists.onebuilding.org
> <mailto:equest-users at lists.onebuilding.org>
> *Subject:* [Equest-users] Section 179D Question
>
> Has anyone run a baseline building for a retrofit building to
> qualify a business owner for the Section 179D tax deduction? It
> seems simple enough to model the existing building based on ASHRAE
> 90.1 standards. Has anyone found any potential "hiccups" along
> the way that has prevented the up to $1.80/sq tax deduction aside
> from the obvious of not meeting the energy upgrade percentage?
>
> Here's my main concern. I have a cabinet manufacturer customer
> who has a 100,000sf metal building that is roughly 30% wood
> working or manufacturing, 65% warehouse storage and 5% office
> space. 95% of this facility is heated only. Do I have to include
> cooling in the baseline from ASHRAE 90.1 system 5 on appendix G,
> table G3.1.1.A? The only upgrades we are proposing are to take
> out the air rotation unit and radiant tube vacuum systems and a
> few other minor items.
>
> Any advice would help. Thanks in advance.
>
> Thanks,
>
> Tom Mickley
>
> Mechanical Engineer CEM
>
> The K Company
>
> Cell 330-760-3994
>
> Office 330-773-5125
>
>
>
>
> _______________________________________________
>
> Equest-users mailing list
>
> http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org
>
> To unsubscribe from this mailing list send a blank message toEQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG <mailto:EQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG>
>
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20140425/f94d6da2/attachment-0002.htm>
More information about the Equest-users
mailing list