Agreed- I have models with 24 hour runs with CFD 60 timesteps for PCM's running now- 



Jeremiah D. Crossett
CleanTech Analytics
503-688-8951
www.cleantechanalytics.com


This document may contain valuable information proprietary to CleanTech Analytics which is private and confidential. It may not be shared, copied, stored or transmitted in any form without the prior written consent of CleanTech Analytics




On Tue, Jun 12, 2012 at 10:20 PM, Jean marais <jeannieboef@xxxxxxxxx> wrote:
 

Found the problem.
1) used FiniteDifferenceMethod and got convergence of a very thick heated floor slab -- effect on problem...small
2) Found that the Load Averaging Window was set to 12 for a 60 TimeStep simulation. Reset to 1 -- effect on problem...large
This is a lesson I will not soon forget.

Note: It seems FDM may be a good way of tackling thick constructions, but be aware that it takes ages longer to simulate.




__._,_.___


Primary EnergyPlus support is found at:
http://energyplus.helpserve.com or send a message to energyplus-support@xxxxxxxx

The primary EnergyPlus web site is found at:
http://www.energyplus.gov

The group web site is:
http://groups.yahoo.com/group/EnergyPlus_Support/

Attachments are currently allowed but be mindful that not everyone has a high speed connection.  Limit attachments to small files.

EnergyPlus Documentation is searchable.  Open EPlusMainMenu.pdf under the Documentation link and press the "search" button.




Your email settings: Individual Email|Traditional
Change settings via the Web (Yahoo! ID required)
Change settings via email: Switch delivery to Daily Digest | Switch to Fully Featured
Visit Your Group | Yahoo! Groups Terms of Use | Unsubscribe

__,_._,___