Name | Ice Tank | |
Availability Schedule Name | ON | |
Capacity | 0.5 | |
Inlet Node Name | Ice Tank Inlet Node | |
Outlet Node Name | Ice Tank Outlet Node | |
Discharging Curve Object Type | QuadraticLinear | |
Discharging Curve Name | DischargeCurve | |
Charging Curve Object Type | QuadraticLinear | |
Charging Curve Name | ChargeCurve | |
Timestep of the Curve Data | 1 | |
Parasitic Electric Load During Discharging | 0.0001 | |
Parasitic Electric Load During Charging | 0.0002 | |
Tank Loss Coefficient | 0.0003 | |
Freezing Temperature of Storage Medium | 23 | |
Name | DischargeCurve | ChargeCurve |
Coefficient1 Constant | 0 | 0 |
Coefficient2 x | 0.09 | 0.09 |
Coefficient3 x**2 | -0.15 | -0.15 |
Coefficient4 y | 0.612 | 0.612 |
Coefficient5 x*y | -0.324 | -0.324 |
Coefficient6 x**2*y | -0.216 | -0.216 |
Minimum Value of x | 0 | 0 |
Maximum Value of x | 1 | 1 |
Minimum Value of y | 0 | 0 |
Maximum Value of y | 9.9 | 9.9 |
Minimum Curve Output | ||
Name | Cooling Supply Outlet | |
Maximum Flow Rate | 0 | |
Pressure Drop Curve Name | ||
Component 1 Object Type | ThermalStorage:Ice:Detailed | |
Component 1 Name | Ice Tank | |
Component 1 Inlet Node Name | Ice Tank Inlet Node | |
Component 1 Outlet Node Name | Ice Tank Outlet Node | |
Component 1 Branch Control Type | PASSIVE | |
Component 2 Object Type | Pipe:Adiabatic | |
Component 2 Name | Supply Side Outlet Pipe | |
Component 2 Inlet Node Name | Ice Tank Outlet Node | |
Component 2 Outlet Node Name | CW Supply Outlet Node | |
Component 2 Branch Control Type | PASSIVE | |
Component 3 Object Type | ||
Component 3 Name | ||
Component 3 Inlet Node Name |