RE: [EnergyPlus_Support] poll item (Ensure Air Mass Conservation in a Zone)





Hi Ery,

 

The main issue is that so-called simple airflows are not necessarily balanced with HVAC flows.  It is complicated to explain, but for example a user could input a set of ZoneMixing objects that don’t balance out with the air handler.

 

From: EnergyPlus_Support@xxxxxxxxxxxxxxx [mailto:EnergyPlus_Support@xxxxxxxxxxxxxxx] On Behalf Of Ery Djunaedy
Sent: Thursday, July 19, 2012 3:19 PM
To: EnergyPlus MAILIST
Subject: [EnergyPlus_Support] poll item (Ensure Air Mass Conservation in a Zone)

 

 

All,

In the latest poll, there is one intriguing item for me:
Ensure Air Mass Conservation in a Zone (all airflows including HVAC,
exhaust, zone mixing, infiltration, etc.)

Does this mean that at the current state of development, EnergyPlus does
not ensure air mass conservation in a zone? I do not know what the poll
item means, I guess. Can someone elaborate on this? Which part of the
manuals I should read that indicate there is potentially a violation of
mass conservation in a zone?

Thanks,

Ery



__._,_.___


Primary EnergyPlus support is found at:
http://energyplus.helpserve.com or send a message to energyplus-support@xxxxxxxx

The primary EnergyPlus web site is found at:
http://www.energyplus.gov

The group web site is:
http://groups.yahoo.com/group/EnergyPlus_Support/

Attachments are currently allowed but be mindful that not everyone has a high speed connection.  Limit attachments to small files.

EnergyPlus Documentation is searchable.  Open EPlusMainMenu.pdf under the Documentation link and press the "search" button.




Your email settings: Individual Email|Traditional
Change settings via the Web (Yahoo! ID required)
Change settings via email: Switch delivery to Daily Digest | Switch to Fully Featured
Visit Your Group | Yahoo! Groups Terms of Use | Unsubscribe

__,_._,___