Bereket,
Thanks for your help. I made the suggested changes, but unfortunately the crash persists. I also have double checked the example file and mine seems to be setup as it should- but evidently is not. Any further suggestions would be appreciated.
Thanks again
Jeremiah D. Crossett | Senior Analyst | Phase Change Energy Solutions120 E. Pritchard St. | Asheboro, NC 27203| Mobile 503-688-8951
On Sun, Dec 8, 2013 at 6:34 AM, Bereket Nigusse <nigusse_ba@xxxxxxxxx> wrote:
You have zone inlet node (SPACE4-1 In Node) specified in the in a Zone Inlet NodeList "SPACE4-1 In Nodes" but not defined/used any where else. Remove/comment out the node "SPACE4-1 In Node" from the list.Only one splitter is allowed in "AirLoopHVAC:SupplyPath". You have unused splitter but defined in the idf. Comment out the unused "Zone Supply Air Splitter 1" object.
These two correction will remove the sever errors.Bereket
On Sunday, December 8, 2013 12:18 AM, Jeremiah Crossett <jcrossett@xxxxxxxxxxxxxxx> wrote:
I copied the heat pump water heater info into a file and modified a bit. Everything looks correct, but it crashes and does not give any good clues to solve the problem..If anyone could take a look at the node connections and let me know what I am doing wrong it would be appreciated.Jeremiah D. Crossett | Senior Analyst | Phase Change Energy Solutions