[Equest-users] Ventilation Energy
Pasha Korber-Gonzalez
pasha.pkconsulting at gmail.com
Wed Sep 11 13:28:23 PDT 2013
Hi Dave, I use the quick and dirty way for peak vent loads from the SV-A
report using the multiplier of the supply cfm and the OA% values at the top
of the report. You can also compare the peak Vent CFM at the zone level at
the bottom of the report where they show the OA CFM for each zone.
Does anybody else use hourly reports to compile the Ventilation data?
Pasha
www.korberenergyconsultants.com
On Wed, Sep 11, 2013 at 1:21 PM, The Watt Doctors - Dave Weigel <
Dave.Weigel at thewattdoctors.com> wrote:
> Hi eQuest Group,
>
> I was wondering if there is a quick way to determine how much of the
> projected energy use in a building is due to conditioning of ventilation
> air? I have scoured through the eQuest reports and detailed simulation
> output but no luck (unless I’m missing something). I suppose I can run the
> simulation again with ventilation set to zero, but it would be great if it
> could be drawn straight from the simulation output.
>
> Thanks!
>
> Dave
>
>
> *David R. Weigel, PE*
> Managing Member
> 1189 Golden Circle SW, Lilburn GA 30047
> 678-353-6394 office 901-619-1716 cell
> [image: wattdoxemailsiglogo(transparent_gif)]
>
>
> _______________________________________________
> Equest-users mailing list
> http://lists.onebuilding.org/listinfo.cgi/equest-users-onebuilding.org
> To unsubscribe from this mailing list send a blank message to
> EQUEST-USERS-UNSUBSCRIBE at ONEBUILDING.ORG
>
>
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.onebuilding.org/pipermail/equest-users-onebuilding.org/attachments/20130911/5794ae1e/attachment-0001.htm>
More information about the Equest-users
mailing list