Re: [EnergyPlus_Support] please help a crashing simulation
At 04:53 PM 1/15/2003, Phelps, Andrew T ERDC-CERL-IL Contractor wrote:
>I just uploaded my IDF (Aec_base.idf) in the files section of the group.
>
Andy,
The problem appears to have been in the following block:
ZONE SPLITTER,
Zone Supply Air Splitter 1, !- Splitter Name
Zone Eq In Node, !- Inlet_Node
ZONE 1 ATU In Node, !- Outlet_Node_1
ZONE 2 ATU In Node; !- Outlet_Node_2
In your input file, you don't have a ";" in the last line. The "audit.out"
file might have showed something here but it scooped the following block
(Air Primary Loop) in without comment.
There are also some severe errors that you should address:
** Severe ** Base surface does not surround subsurface (CHKSBS)
** ~~~ ** Surface "ZN002:ROOF001" misses SubSurface
"ZN002:ROOF001:WIN002"
** Severe ** Base surface does not surround subsurface (CHKSBS)
** ~~~ ** Surface "ZN002:ROOF001" misses SubSurface
"ZN002:ROOF001:WIN005"
** Severe ** Base surface does not surround subsurface (CHKSBS)
** ~~~ ** Surface "ZN002:ROOF001" misses SubSurface
"ZN002:ROOF001:WIN006"
** Severe ** Base surface does not surround subsurface (CHKSBS)
** ~~~ ** Surface "ZN002:ROOF001" misses SubSurface
"ZN002:ROOF001:WIN010"
** Severe ** Base surface does not surround subsurface (CHKSBS)
** ~~~ ** Surface "ZN002:ROOF001" misses SubSurface
"ZN002:ROOF001:WIN011"
** Severe ** Base surface does not surround subsurface (CHKSBS)
** ~~~ ** Surface "ZN002:ROOF001" misses SubSurface
"ZN002:ROOF001:WIN012"
** Severe ** Base surface does not surround subsurface (CHKSBS)
** ~~~ ** Surface "ZN002:ROOF001" misses SubSurface
"ZN002:ROOF001:WIN013"
Linda
EnergyPlus WebSite: http://www.energyplus.gov
Owner: EnergyPlus_Support list
Member: EnergyPlus Development Team
------------------------ Yahoo! Groups Sponsor ---------------------~-->
Flexible Keyboard is the ideal accessory for PDA users that are on the move.
http://us.click.yahoo.com/dCBVZC/WnCFAA/xGHJAA/dkFolB/TM
---------------------------------------------------------------------~->
To unsubscribe from this group, send an email to:
EnergyPlus_Support-unsubscribe@xxxxxxxxxxxxxxx
The primary EnergyPlus web site is found at:
http://www.energyplus.gov
The group web site is:
http://groups.yahoo.com/group/EnergyPlus_Support/
Attachments are not allowed -- please post any files to the appropriate folder in the Files are of the Support Web Site.
Your use of Yahoo! Groups is subject to http://docs.yahoo.com/info/terms/