[EnergyPlus_Support] Re: HeatExchanger:Desiccant:BalancedFlow wrong temperature and humidity results





Hi again !

To be more accurate about my problem, I join the performance data of the Desiccant object.

For instance, with the following points and the performance datas attached:
RWI (Regen Water ratio Inlet) = 12 g/kg
RTI (Regen Temperature Inlet) = 70 °C
PWI (Process Water ratio Inlet) = 15 g/kg
PTI (Process Temperature Inlet) = 34 °C

Energyplus simulation gives me the following outlets:
RWO (Regen Water ratio Outlet) = 18.5 g/kg
RTO (Regen Temperature Outlet) = 43.4 °C
PWO (Process Water ratio Outlet) = 8.5 g/kg
PTO (Process Temperature Outlet) = 60.5 °C

whereas equations to find RWO and RTO given by the Engineering Reference document give me:
RWO (Regen Water ratio Outlet) = 21.2 g/kg
RTO (Regen Temperature Outlet) = 29.1 °C
PWO (Process Water ratio Outlet) = 5.7 g/kg
PTO (Process Temperature Outlet) = 74.9 °C

The mass flow rate was 2100 m3/h (balanced)

Is there a problem in Performance Data ?

Best Regards
TM


__._,_.___

Posted by: tommathelin@xxxxxxxxx


EnergyPlus support is found at:
http://energyplus.helpserve.com or send a message to energyplus-support@xxxxxxxx

The EnergyPlus web site is found at:
http://www.energyplus.net/

The group web site is:
http://groups.yahoo.com/group/EnergyPlus_Support/

Attachments are currently allowed but be mindful that not everyone has a high speed connection.  Limit attachments to small files.

EnergyPlus Documentation is searchable.  Open EPlusMainMenu.pdf under the Documentation link and press the "search" button.




Visit Your Group
Yahoo! Groups
PrivacyUnsubscribeTerms of Use

__,_._,___
Attachment Converted: "D:\Eudora\Attach\DEC rotor Energyplus.idf"