[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]
RE: [EnergyPlus_Support] GrndTempCalc: building not temperature controlled
OK, I think I've got it:
- modify my own building model so all the Ground surface have full insulation (like R-40)
- use no GroundTemperature data in my building model
- run my building model and note all the monthly average zone air temperatures
- different zones are different sizes. Use each one as input to GrndTempCalc and weight that zone as a percentage of the whole slab exposure area and get an overall monthly indoor air temperature
- run GrndTempCalc with those weighted monthly average air temperatures.
- Use the data structure in the .grp file to define the Core and Perimeter GroundTemperature data.
OK, good.
- another sunny day in the land of the blue sky
__._,_.___
Posted by: bvonmoss@xxxxxxxxx
Primary EnergyPlus support is found at:
http://energyplus.helpserve.com or send a message to energyplus-support@xxxxxxxx
The primary EnergyPlus web site is found at:
http://www.energyplus.gov
The group web site is:
http://groups.yahoo.com/group/EnergyPlus_Support/
Attachments are currently allowed but be mindful that not everyone has a high speed connection. Limit attachments to small files.
EnergyPlus Documentation is searchable. Open EPlusMainMenu.pdf under the Documentation link and press the "search" button.